Transient Stability of Paralleled Virtual Synchronous Generator and Grid-following Inverter
  • +2
  • Si Phu Me ,
  • Milad Zarif Mansour ,
  • Sasan Zabihi ,
  • Behrooz Bahrani ,
  • Mohammad Hasan Ravanji
Si Phu Me
Monash University, Monash University

Corresponding Author:[email protected]

Author Profile
Milad Zarif Mansour
Author Profile
Sasan Zabihi
Author Profile
Behrooz Bahrani
Author Profile
Mohammad Hasan Ravanji
Author Profile

Abstract

The majority of inverter-based resources (IBRs) currently operate as grid-following inverters (GFLIs). These inverters exhibit certain stability issues when integrated in low-strength areas of the grid. To enhance the grid strength in a GFLI-dominant area, virtual synchronous generators (VSGs) are installed. If the VSG and the GFLI are investigated as a paralleled system, despite the benefits brought by the VSG, in some cases, the transient angle instability process, caused by a voltage sag, is accelerated. Therefore, this paper studies the transient angle stability of a paralleled VSG-GFLI system via investigating the voltage at a common bus between the two IBRs. Subsequently, a stable region of the voltage angles of the two IBRs is determined. Based on this region, the stability margin of the paralleled system can be determined and used to quantitatively evaluate the system stability. Moreover, a control loop is proposed to improve the transient stability of the paralleled system. The proposed controller can adaptively reduce the VSG power set-point to avoid a complete failure of the VSG even when no stable equilibrium point exists during a voltage sag. The stability investigation and performance evaluation of the proposed method are conducted in PSCAD/EMTDC and experimentally validated.
Nov 2023Published in IEEE Transactions on Smart Grid volume 14 issue 6 on pages 4451-4466. 10.1109/TSG.2023.3255168